• Home
  • /
  • Blog
  • /
  • I have a questions about the Phase Differential settings for the GE Multilin SR-489

I have a questions about the Phase Differential settings for the GE Multilin SR-489

GE Multilin SR-489

I have a questions about the Phase Differential settings for the GE Multilin 489

Diff. Trip Min. P.U. is — 0.10 X CT

What are they  referring  to the CTR 3200/5 or the Generator

Diff. Trip Slope 1— 10%
Diff. Trip Slope 2— 20%

Are they referring to Full Load Amps of the Gen

Generator Parameters are
FLA = 3007
2.5 MVA
.8 PF
480 Volt
CTR 3200/5
NCTR 3200/5

Thanks for any help

arnie1977

 Did you like this post?

You can share it with these links:

About the Author

Chris is an Electrical Engineering Technologist, a Journeyman Power System Electrician, and a Professional Engineer. He is also the Author of The Relay Testing Handbook series and founder of Valence Electrical Training Services. You can find out more about Chris here.

Read More Articles:

Leave a Reply

Your email address will not be published.

  1. It should be 0.1 x CT where CT is the maximum secondary current of the CT, typically 5 A in north America. 0.1 x 5A = 0.5 A pick up. Some GE relays will also add the difference between taps of windings as an additional multiplier but generator windings typically have the same CT ratio so that factor will not apply.

    It is important that you perform the pickup test using three phase balanced currents because a single phase test may add correction factors such as 1.73, 1.5, 1.414 depending on the relay.

    1. Dear Chris,

      My comment is a year on the road, but still…

      The 0.1PU should be a guiding number referring to actual currents. CTs are sometimes set higher then the Gen I-nominal (FLA), so, the 0.1 PU starts to loose relevancy for the specific Gen, and therefor, not adequately protecting it.

      N.B. in case the zone of protection includes a Transformer, the CTs will have different ratios, and compensations will be done in the relay setting file and not externally (as per GE guide).

      Kind regards,

      Eric Stark
      RNItechnology
      Sr. Eng. Trainer & Consultant
      Protection & Control Engineering
      T: 1-416-546-546-1
      [email protected]
      http://www.RNItechnology.com
      LinkedIn profile @: ca.linkedin.com/pub/eric-stark/2b/143/b7

{"email":"Email address invalid","url":"Website address invalid","required":"Required field missing"}