Help with 27/47/59N Protection in an SEL-387E

A reader has requested some help for an upcoming project: I will be reviewing some relay testing that needs to performed shortly and I am trying to understand how the 27/47/59N (within a SEL 387E) relay function is being applied. The 387E provides the 87T function for the 115KV to

Read More
Help with 27/47/59N Protection in an SEL-387E

What Electromechanical Relay Kicked Your Ass?

Induction Disc Relay - Electro-mechanical Relay picup

I’m writing a blog post to help people buy a protective relay test-set that’s right for their application. What electromechanical relays require the most VA, or compliance voltage, to test? I want to make a list so that buyers can look at their inventory and pull those relays out when

Read More
What Electromechanical Relay Kicked Your Ass?

CT Primary Injection Ratio Testing Problems

CT Primary Injection

Situation after CT Primary Injection: New 230kv breaker Testing CT’s, 4000/5, by high current injection injecting 80 amps A phase to ground the secondary leads are shorted in a junction box A-B-C-N / additionally a voltage is connected to test instrument form test set The secondary readings are A = 0.096

Read More
CT Primary Injection Ratio Testing Problems

SEL-321 Out-of Step Protection Problem?

Out of Step Protection Blinders

SEL 321 OSB upper tests fine, lower is no-op but 51g comes in any ideas? I’m oversight on a project, test company is using a Doble 6150 w/ RTS, I’m not very familair with RTS sdg

Read More
SEL-321 Out-of Step Protection Problem?

ASEA RAGEA 27N Gen Neutral Undervoltage

ASEA RAGEA 27N Gen Neutral Undervoltage

I can not find up dated information on this relay. I am testing with a manta 5000. I put 60 vac 60 hz on leads 7 and 8 and the relay picks up. Then on lead 11 & 12 I put 180 Hz and bring up vac to 1.27 and

Read More
ASEA RAGEA 27N Gen Neutral Undervoltage

SBF-1 Westinghouse Breaker Failure Relay Failure Question

SBF-1

To all, We had a SBF-1 Breaker Failure Relay fail on us yesterday.  The time delay was not working properly.  We have many of these relays on our system and wanted to see if there has been a Relay Advisory, or PAL letter on this relay.  Would also like to

Read More
SBF-1 Westinghouse Breaker Failure Relay Failure Question