Connect to a Electro Industries Futura+ Series CPU1000

Futura+ Series CPU1000

Cable:        9-pin to 9-pin RS-232 Straight Through Software:   Futura+ Communicator Settings:     Default Settings Link:          Direct Connection Device Address: 0001 Communications Port: COM1 (Varies by Computer) Baud Rate: 9600 Protocol: EI Protocol Make sure the switch beside the comm port on the meter

Read More
Connect to a Electro Industries Futura+ Series CPU1000

What Relay Test Equipment Do You Use and Why?

Relay Test Equipment

This post is pretty old.  I suggest you check this post to get a better idea of my thoughts on test-sets.  https://relaytraining.com/what-is-the-best-protective-relay-test-set/ I understand Chris has a Manta MTS-5000, do you like it! Does anyone else has info on the Manta? What about other test equipment? Thanks for any info you

Read More
What Relay Test Equipment Do You Use and Why?

Reset SEL relays to Factory Defaults

SEL Relays

The DC Power supply to the relay quit in the middle of a setting download and when the power was restored, the relay EEprom failed.  I was able to communicate with the relay (at a different BAUD rate) and the SEL Tech support had me go to level 2 and

Read More
Reset SEL relays to Factory Defaults

How to Connect to a Beckwith Electric M-3425 Relay

M-3425 Relay

http://www.beckwithelectric.com/ Beckwith M-3425 Generator protection Cable: 9-pin to 9-pin RS-232 Null Modem Software: 3820A IPScom Communications Software Software Default Settings PC Port: Com1 (Varies by Computer) Baud Rate: 9600 Echo Cancel: Not Selected Access Code: Default Address: 1 Make sure that the screen is blank and you have completely exited

Read More
How to Connect to a Beckwith Electric M-3425 Relay

How to Connect to a BE1-GPS100

BE1-GPS100

  Basler GPS100 Relay   Cable: 9-pin to 9-pin RS-232 Straight through Software: Basler Bestcomms software for GPS100 Software Default Settings Comm Port: 1 Varies by Computer (Doesn’t seem to work with Comm 2) Baud Rate: 9600 Parity: None Data Bits: 8 Stop Bits: 1 Show Commands During Transfer: Off

Read More
How to Connect to a BE1-GPS100