CT Primary Injection Ratio Testing Problems

Situation after CT Primary Injection:
New 230kv breaker
Testing CT’s, 4000/5, by high current injection
injecting 80 amps A phase to ground
the secondary leads are shorted in a junction box A-B-C-N / additionally a voltage is connected to test instrument form test set
The secondary readings are A = 0.096 @ 176 degrees, B = 0.01 @ 0, C = 0.01 @ 0, N = 0.108 @ 4
only one set of CT’s, 2 per phase read this all others tested where i.e. A=0@0, B=0.1@180, C=0@0, N=0.1@0

When load was applied secondary current looked correct
Seems like I ‘ve seen this before, is there an answer for this?
Electricity is a Theory……………right?
sdg


Discover more from Valence Electrical Training Services

Subscribe to get the latest posts sent to your email.

 Did you like this post?

You can share it with these links:

About the Author

Chris is an Electrical Engineering Technologist, a Journeyman Power System Electrician, and a Professional Engineer. He is also the Author of The Relay Testing Handbook series and founder of Valence Electrical Training Services. You can find out more about Chris here.

Read More Articles:

A New Transmission Line Protection (21) Video

Leave a Reply

  1. Chris,
    The A phase readings were not as expected.
    They were not seeing the entire value on A and B&C small amount and the N was high
    When testing the other phases the readings were full current on tested phase and N with zero on other phases

    Kind of looks like the CT is not centered on the bushing or possible bad cable or some other interaction

    Thoughts?

    Steve

  2. I don’t perform primary injection tests because the values always seemed to me to be small to be reliable. I can’t think of a theoretical reason why CT position compared to primary conductor should matter.

    My gut tells me that you saw an induced current or ground current. Isolating the CT ground from ground for the test might make a difference.

  3. Thanks Chris!

    Yes the connection that they used through ground back to the test set is likely the issue

    Steve