How to Connect to a GE LPS Relay

GE LPS

GE LPS

Cable: 9-pin to 9-pin RS-232 Null Modem
Software: EnerVista ALPS/LPS/LPS-O Setup

Software Default Settings
Unit ID: 0000
Baud Rate: 9600
Data Bits: 8
Stop Bits: 1
Parity: None
Break Signal: Do Not Select
Duration of Break: 0
Phone No: “” (Blank)
Auxiliary Phone: “” (Blank)
Connection: RS-232
Switch Code: “” (Blank)

Passwords & Connection Info
Password is “CONTROL!” from factory and will only allow you to change password to something else.
Password is “MASTER!” from factory and will only allow you to change password to something else. Then LOG In and change settings change password back to “MASTER!”

Testing Info

  1. Metering angles will be off by 30 degrees
  2. All tests must be performed using all three phases.  Single-phase and Phase-Phase tests will not work.