• Home
  • /
  • Blog
  • /
  • Possible Winding Voltages Setup Issue With GE Multilin 745 Transformer Management Relay

Possible Winding Voltages Setup Issue With GE Multilin 745 Transformer Management Relay

GE Multilin 745 Transformer Management Relay

This was a nice surprise for me.  Older versions of the SR-745 have a maximum voltage of 200kV.  If you use newer software to set the relay, it indicates a maximum voltage of 2000.0 kV.  If a voltage setting higher than the maximum is uploaded, the relay automatically divides all voltage and MVA values by a factor of 10.  There is NO warning when this happens.  This fix does work but will be a shock when someone else looks at the settings afterward.  A good fix is to change the voltages to line to ground values.


Discover more from Valence Electrical Training Services

Subscribe to get the latest posts sent to your email.

 Did you like this post?

You can share it with these links:

About the Author

Chris is an Electrical Engineering Technologist, a Journeyman Power System Electrician, and a Professional Engineer. He is also the Author of The Relay Testing Handbook series and founder of Valence Electrical Training Services. You can find out more about Chris here.

Read More Articles:

Reset SEL relays to Factory Defaults

Leave a Reply

{"email":"Email address invalid","url":"Website address invalid","required":"Required field missing"}